Schneider Electric 61 Network Router User Manual


 
63
Configuration saving and switching
Function parameters
Code Description
CNF1 Parameter name: Assignment for 2 configurations
Terminal display: [2 Configurations]
Logic address: 8021 = 16#1F55 Type: WORD (listing)
CANopen index: 2032/16 Read/write: R/WS
INTERBUS index: 5FBC/9C Factory setting: 0
DeviceNet path: 9C/01/9C
See next page.
CNF2 Parameter name: Assignment for 3 configurations
Terminal display: [3 Configurations]
Logic address: 8022 = 16#1F56 Type: WORD (listing)
CANopen index: 2032/17 Read/write: R/WS
INTERBUS index: 5FBC/9D Factory setting: 0
DeviceNet path: 9C/01/9D
See next page.
CNFS Parameter name: Active configuration
Terminal display: [Config. active]
Logic address: 8020 = 16#1F54 Type: WORD (listing)
CANopen index: 2032/15 Read/write: R
INTERBUS index: 5FB9/D1
DeviceNet path: 89/01/15
0 = The parameter set switching function is not configured
1 = (CNF0): Configuration no. 0 active
2 = (CNF1): Configuration no. 1 active
3 = (CNF2): Configuration no. 2 active
Value of the control bit assigned by [2 Configurations] (CnF1) 0 1 0 1
Value of the control bit assigned by [3 Configurations] (CnF2) 0 0 1 1
Value of [Config. active] (CnFS) 1 2 3 3
Active configuration 0 1 2 2