5. Secure the PCI card using one of the following two methods:
If the slot has an MRL, close the MRL and push down on it until it clicks.
If the slot does not have an MRL, replace the retaining bracket and its single
securing screw to the top of the card.
6. Before re-installing the cover on the server, check the routing of all cables for
obstructions.
4.5.1.5 Installing a Horizontal PCI Card and Riser
Follow these steps to install a horizontal-mount PCI card (see FIGURE 4-5 for the
location). The server has one horizontal slot located under the power-supply cage
assembly that supports one half-length, 66-MHz PCI card.
1. Power off the server, including any attached peripherals, and disconnect the
server from the electrical outlet. If your server includes two power supplies,
ensure that both power cords are disconnected from the electrical outlet.
Refer to “Powering Off the Server and Removing the Cover” on page 4-2.
2. Remove the power-supply cage assembly: see “Replacing a Power-Supply Cage
Assembly” on page 4-39.
3. On the outside of the server back panel, loosen the screw holding the card latch
(see
FIGURE 4-8).
4. Raise the card latch as far as possible and then pivot it towards the rear of the
chassis.
FIGURE 4-8 Removing or Installing a Horizontal PCI Card
5. Remove any existing PCI card from the PCI riser. If the slot is blank, remove its
metal slot cover from the server back panel.