Sun Microsystems V20z Server User Manual


 
Chapter 4 Maintaining the Sun Fire V40z Server 4-33
2. Remove the main air baffle (see FIGURE 4-20).
Lift the rear edge of the baffle, then move it toward the rear of the server to
disengage the hooks on the front edge of the baffle.
3. Identify the fan(s) to be replaced in either the front or rear fan cage.
4. Squeeze the retainer clip on the edge of the fan, then pull the fan straight up to
disengage its connector and remove it from its fan cage (see
FIGURE 4-23).
FIGURE 4-23 Removing an Individual Cooling Fan (Cage Shown Removed From Server)
5. To install a new fan, align it with the bay in the fan cage and push down firmly
and evenly on both top corners of the fan to engage it with the cage connector.
Caution – Ensure that the fan airflow direction is correct (front to rear) by installing
the fan so that the airflow direction arrow points towards the rear of the chassis.
After installing a new fan, allow sufficient time for the system to recognize the fan
and to determine whether it is functioning properly.
6. Before re-installing the cover on the server, check the routing of all cables for
obstructions.