Symmetricom 1100 Clock User Manual


 
097-58001-02 Revision G – April 2008 TimeProvider User’s Guide 131
Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
Sample Command
ED-SYNC::SYS:TS1000::CLRDELAY=5;
This command declares a faulted input to be valid five seconds after the alarm
condition has cleared.
Autonomous Message
TP-SSU 03-10-24 11:18:00
A 1192 REPT EVT
“SYS,EQPT:NA,CLRDELAY,NSA,03-10-24 11-18-00:\"INPUT CLEAR
DELAY HAS CHANGED\””
;
Retrieving Current Alarm Settings
You can display the current settings for any alarm using the RTRV-ATTR command.
RTRV-ATTR:[<tid>]:<aid>:[<ctag>][::<keyword>];
This command always has an access level of USER.
SYS
(cont’d)
GPSCLRDEL
0 to 1000 s
Sets the time delay to
declare GPS is valid after
an alarm condition clears
5
GPSFLTDEL
1 to 1000 s
Sets the time delay before a
GPS fault is declared
1
<aid> <keyword> Description
SYS ELEVTIME ENABLE | DISABLE
SYS
IMC
IOC
PRS
INPp (p = 1 | 2)
Alarm ID The Alarm ID is described in Provisioning
the Alarm Levels, on page 126
ALL (or null) ALL (or null) Returns all of the alarm attributes
<aid> <keyword> <value> Description Default value