Symmetricom 1100 Clock User Manual


 
097-58001-02 Revision G – April 2008 TimeProvider User’s Guide 93
Chapter 4 Provisioning the TimeProvider
Setting Communications Parameters
Setting Ethernet Parameters
Before you can begin using the Ethernet port, you must provision the addresses
using the local Craft or Remote serial port.
If you are not planning to use the Ethernet port, you do not have to provision the
parameters in this section.
Setting the IP Addresses
Use the ED-EQPT command to provision the following IP addresses for the
TimeProvider:
IP Gateway address
IP address
IP subnet Mask
ED-EQPT:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
Sample Command
ED-EQPT::COMI:TS1000::IPGATE=127.0.0.1;
This command sets the IP Gate address to 127.0.0.1. Use an appropriate gateway
address for your network, and record the address in Table 4-4.
Autonomous Message
TP-SSU 03-10-24 10:15:04
A 1169 REPT EVT
“COMI:NA,IPGATE,NSA,03-10-24 10-15-04:\”IP GATEWAY
ADDRESS HAS CHANGED\””
;
Note: To avoid unexpected interruptions in NTP service, you must
restart the IMC card after you change either the Subnet Mask or the
IP Address when NTP is active.
<aid> <keyword> <value> Description Default
COMI IPGATE 1.0.0.1
254.255.255.254
IP address of the default gateway 127.0.0.1
IPADDR 1.0.0.1
254.255.255.254
IP address of the Network
Element
127.0.0.1
IPSUBNET 1.0.0.1
255.255.255.254
Subnet mask IP address 255.255.
255.0