W7 ASD Installation and Operation Manual 95
Overvoltage Stall Level (fast)
Program Protection Settings Overvoltage Stall Level (fast)
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the ASD during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.
If the overvoltage condition persists for over 250 µS, an Overvoltage Trip will
be incurred.
Note: This feature may increase deceleration times.
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 250.0
Units — %
Panel Acceleration/Deceleration Select
Program Panel Control Panel Acceleration/Deceleration Select
This parameter is used to select 1 of 4 accel/decel profiles that may be
configured and run. Each accel/decel profile is comprised of 3 user settings:
Acceleration, Deceleration, and Pattern.
Settings:
Acceleration/Deceleration #1
Acceleration/Deceleration #2
Acceleration/Deceleration #3
Acceleration/Deceleration #4
Parameter Type — Selection List
Factory Default — Acceleration/
Deceleration #1
Changeable During Run — Yes
Panel Direction
Program Panel Control Panel Direction
This parameter sets the motor direction while operating from the keypad.
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
Panel Operation Inhibit Selection
Program Utilities Display Attributes Panel Operation Inhibit
Selection
This parameter disables the selected keypad function.
Settings:
Allow All Keys
Allow Emergency Off Only
Parameter Type — Selection List
Factory Default — Allow All Keys
Changeable During Run — Yes
Panel PID Control
Program Panel Control Panel PID Control
Enables/Disables PID control while operating from the keypad.
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Panel Reset Selection
Program Panel Control Panel Reset Selection
Enables/Disables the ability to reset the system from the keypad.
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes