Number of Retries
Program Protection Settings Number of Retries
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the Retry function:
OCA1, 2, or 3 (Arm Short Ckt),
EPH1 (Input Phase Failure),
EPH0 (Output Phase Failure),
OCL (Startup Overcurrent),
EF1 or 2 (Ground Fault),
EMG (Emergency Off),
EEP1 (EEPROM Fault),
Err2 through Err9 (Main RAM/ROM Fault),
E-10 (Sink/Source Error),
13 (Speed Error), or
17 (Key Error).
See the section titled General Safety Information on pg. 1 for further
information on this setting.
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 10
ON Terminal
Program Terminal Settings Input Terminals ON
This parameter selects the functionality of the ON discrete input virtual
terminal.
As a virtual terminal, the ON control terminal exists only in memory and is
considered to always be in its True (or connected to CC) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to 1 of the 69 possible
functions that are listed in
Table 6 on page 138.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
OUT1 Off Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT1 OUT1 Off Delay
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
FL Off Delay).
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Number of Retries OUT1 Off Delay