Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 135
VI/II Speed Frequency Setpoint #2
Program Frequency Settings Speed Reference Setpoints VI/II
VI/II Speed Frequency Setpoint #2
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control mode.
See VI/II Speed Frequency Setpoint #1 for further information on this setting.
This parameter sets VI/II Speed Frequency Setpoint #2 and is the frequency
that is associated with the setting of VI/II Speed Reference Setpoint #2 when
operating in the Speed Control mode.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
VI/II Speed Reference Setpoint #1
Program Frequency Settings Speed Reference Setpoints VI/II
VI/II Speed Reference Setpoint #1
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See VI/II Speed Frequency Setpoint #1 for further information on this setting
when used for Speed control.
See VI/II Torque Reference Setpoint #1 for further information on this setting
when used for Torque control.
This parameter sets the VI/II input level that is associated with VI/II Speed
Frequency Setpoint #1 when operating in the Speed control mode or is
associated with the VI/II Torque Reference Setpoint #1 when operating in the
Torque control mode.
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
The default value for this parameter is 20%. The II input is commonly used for
the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal.
If the VI input is used (0 – 10 VDC input), this parameter may be changed to
0.0% (of the input signal).
Parameter Type — Numerical
Factory Default — 20.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Reference Setpoint #2
Program Frequency Settings Speed Reference Setpoints VI/II
VI/II Speed Reference Setpoint #2
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See VI/II Speed Frequency Setpoint #1 for further information on this setting
when used for Speed control.
See VI/II Torque Reference Setpoint #1 for further information on this setting
when used for Torque control.
This parameter sets the VI/II input level that is associated with VI/II Speed
Frequency Setpoint #2 when operating in the Speed control mode or is
associated with the VI/II Torque Reference Setpoint #2 when operating in the
Torque control mode.
This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Frequency Setpoint #2 VI/II Speed Reference Setpoint #2