Toshiba W7 Computer Drive User Manual


 
62 W7 ASD Installation and Operation Manual
Commercial (Power) Wait Time
Program Special Control Comm Wait Time
This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
Parameter Type — Selection List
Factory Default — 0.62
Changeable During Run — No
Minimum — 0.37
Maximum — 10.00
Units — Seconds
Communications Data Type
Program Communication Settings Communication Data Type
In the event of a communication error during a transmission, the command that
was transmitted may be cleared or held.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — No
Communication Interval (TTL)
Program Communication Settings TTL Res Time
This parameter sets the TTL response delay time.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
Commercial (Power) Wait Time Communication Interval (TTL)