98 W7 ASD Installation and Operation Manual
Encoder
PG Speed Frequency Setpoint #2
Program Frequency Settings Speed Reference Setpoints PG
PG Speed Frequency Setpoint #2
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets PG Speed Frequency Setpoint #2 and is the frequency that
is associated with the PG Speed Reference Setpoint #2 setting.
See PG Speed Frequency Setpoint #1 for further information on this setting.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
PG Speed Reference Setpoint #1
Program Frequency Settings Speed Reference Setpoints PG
PG Speed Reference Setpoint #1
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents PG Speed
Frequency Setpoint #1 (direction/speed) and is entered as a percentage of the
full ± range.
The range of values for this parameter is -100 to +100% of the PG input pulse
count range.
See PG Speed Frequency Setpoint #1 for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
PG Speed Reference Setpoint #2
Program Frequency Settings Speed Reference Setpoints PG
PG Speed Reference Setpoint #2
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents PG Speed
Frequency Setpoint #2 (direction/speed) and is entered as a percentage of the
full ± range.
The range of values for this parameter is -100 to +100% of the PG input pulse
count range.
See PG Speed Frequency Setpoint #1 for further information on this setting.
Parameter Type — Numerical
Factory Default — +100.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
PID Feedback
Program System Information and Setup PID Setup PID
Feedback Value
This parameter is read-only and is provided as a quick reference for the user
during PID setup.
PG Speed Frequency Setpoint #2 PID Feedback