Toshiba W7 Computer Drive User Manual


 
102 W7 ASD Installation and Operation Manual
Preset Speed #8
Program Preset Speeds 8
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #9
Program Preset Speeds 9
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #10
Program Preset Speeds 10
This parameter assigns an output frequency to binary number 1010 and is
identified as Preset Speed #10. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #11
Program Preset Speeds 11
This parameter assigns an output frequency to binary number 1011 and is
identified as Preset Speed #11. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #12
Program Preset Speeds 12
This parameter assigns an output frequency to binary number 1100 and is
identified as Preset Speed #12. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #8 Preset Speed #12