108 W7 ASD Installation and Operation Manual
RR Speed Reference Setpoint #1
Program Frequency Settings RR RR Speed Reference
Setpoint #1
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See RR Speed Frequency #1 for further information on this setting when used
for Speed control.
See RR Torque Reference #1 for further information on this setting when used
for Torque control.
This parameter sets the RR input level that is associated with RR Speed
Frequency #1 when operating in the Speed control mode or is associated with
the RR Torque Reference #1 when operating in the Torque control mode.
This value is entered as 0.0 to +100% of the 0 – 10 VDC RR input signal range.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Reference Setpoint #2
Program Frequency Settings RR RR Speed Reference
Setpoint #2
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See RR Speed Frequency #1 for further information on this setting when used
for Speed control.
See RR Torque Reference #1 for further information on this setting when used
for Torque control.
This parameter sets the RR input level that is associated with RR Speed
Frequency #2 when operating in the Speed control mode or is associated with
the RR Torque Reference #2 when operating in the Torque control mode.
This value is entered as 0.0 to +100% of the 0 – 10 VDC RR input signal range.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Reference Setpoint #1 RR Speed Reference Setpoint #2