W7 ASD Installation and Operation Manual 79
Jump Frequency #2
Program Special Control Jump Frequency #2
This parameter establishes the Jump Frequency #2 setting.
Once set up and enabled, it is on in all control modes.
See the Jump Frequency #1 parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Jump Frequency #3
Program Special Control Jump Frequency #3
This parameter establishes the Jump Frequency #3 setting.
Once set up and enabled, it is on in all control modes.
See the Jump Frequency #1 parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Jump Frequency #1 Bandwidth
Program Special Control Jump Frequency #1 Bandwidth
This parameter establishes a plus-or-minus value for Jump Frequency #1.
See the Jump Frequency #1 parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.00
Units — Hz
Jump Frequency #2 Bandwidth
Program Special Control Jump Frequency #2 Bandwidth
This parameter establishes a plus-or-minus value for Jump Frequency #2.
See the Jump Frequency #1 parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump Frequency #3 Bandwidth
Program Special Control Jump Frequency #3 Bandwidth
This parameter establishes a plus-or-minus value for Jump Frequency #3.
See the Jump Frequency #1 parameter for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump Frequency #2 Jump Frequency #3 Bandwidth