Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 67
Direction Priority
Program Terminal Settings Input Terminals Other Direction
Priority Selection
The Direction Priority selection determines the operation of the ASD if both
the R and F control terminals are activated simultaneously.
Settings:
Reverse
Suspend
The waveforms below depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No
Disable Forward Run/Disable Reverse Run
Program Fundamental Parameters Fundamental #1 Disable
Forward/Reverse Run
This parameter Enables/Disables the Forward Run or Reverse Run mode.
If either direction is disabled, commands received for the disabled direction will
not be recognized.
If Command Priority or Off is selected, the received direction command will
determine the direction of the motor rotation.
Settings:
Off
Disable Reverse
Disable Forward
Command Priority
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Direction Priority Disable Forward Run/Disable Reverse Run