Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 91
OUT5 Terminal
Program Terminal Settings Output Terminals OUT5 Terminal
Assignment
This parameter sets the functionality of the OUT5 output contacts to 1 of the 58
possible functions that are listed in
Table 7 on page 141.
The on and off delay times of the OUT5 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Upper Limit
Changeable During Run — No
OUT6 Off Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT6 Off Delay
Once the condition is met to change the state of the OUT6 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at
FL Off Delay).
The on and off delay times of the OUT6 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 On Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT6 On Delay
This parameter delays the response of the OUT6 output contacts by the
programmed value (see waveforms at
FL On Delay).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT6 Terminal
Program Terminal Settings Output Terminals OUT6 Terminal
Assignment
This parameter sets the functionality of the OUT6 output contacts to 1 of the 58
possible functions that are listed in
Table 7 on page 141.
The on and off delay times of the OUT6 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Reach Speed
Changeable During Run — No
OUT7 Off Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT7 Off Delay
Once the condition is met to change the state of the OUT7 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at
FL Off Delay).
The on and off delay times of the OUT7 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT5 Terminal OUT7 Off Delay