Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 89
OUT1 On Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT1 OUT1 On Delay
Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
FL On Delay).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 Terminal
Program Terminal Settings Output Terminals OUT1 Terminal
Assignment
This parameter sets the functionality of the OUT1 (A & C) output contacts to 1
of the 58 possible functions that are listed in
Table 7 on page 141.
The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Damper Cmd
Changeable During Run — No
OUT2 Off Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT2 Off Delay
Once the condition is met to change the state of the OUT2 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at
FL Off Delay).
The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 On Delay
Program Terminal Settings Terminal Delays Output Terminal
Delays
OUT2 On Delay
This parameter delays the response of the OUT2 (A & C) output contacts by
the programmed value (see waveforms at
FL On Delay).
The delay may be increased to prevent relay chatter.
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 Terminal
Program Terminal Settings Output Terminals OUT2 Terminal
Assignment
This parameter sets the functionality of the OUT2 (A & C) output contacts to 1
of the 58 possible functions that are listed in
Table 7 on page 141.
The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output contacts must be specified as Normally Open or
Normally Closed.
Parameter Type — Selection List
Factory Default — Acc/Dec Completion
Changeable During Run — No
OUT1 On Delay OUT2 Terminal