Toshiba W7 Computer Drive User Manual


 
56 W7 ASD Installation and Operation Manual
ASD Wait Time
Program Special Control Inverter Wait Time
This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.
Parameter Type — Read-Only
Factory Default — (ASD-dependent)
Changeable During Run — No
ASD Typeform
Program Utilities Version ASD Type
This parameter is read-only and displays the current typeform configuration of
the ASD.
Parameter Type — Read-Only
Factory Default — (ASD-dependent)
Changeable During Run — No
Autotune Control Setting
Program Motor Settings Autotune Control Setting
When enabled via the Autotune Enable parameter, this parameter sets the
Autotune command status.
Settings:
(Autotune) Disabled
Reset (Motor) Defaults
Enable (Autotune) on Run Command
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Autotune Enable
Program Motor Settings Autotune Enable
This parameter Enables/Disables the Autotune function.
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — No
Base Frequency #1
Program Motor Settings Base Frequency #1
The Base Frequency setting determines the frequency at which the output
voltage of the ASD reaches its maximum setting. The maximum voltage setting
cannot be more that the input voltage (see the
Maximum Output Voltage #1
parameter). There are four Base Frequency profile settings: #1 – #4.
Note: For proper motor operation, the Base Frequency is
normally set for the name-plated frequency of the motor.
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
ASD Wait Time Base Frequency #1