Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 61
Brake Fault Internal Timer
Program Protection Settings Brake Fault Internal Timer
After a brake failure has occurred, the user-set Brake Fault Time clock setting
will begin to count down. Once this time has elapsed, a signal will be provided
to indicate that the brake has failed.
This signal may be used to halt a related system or to notify the user.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Break/Make Auto Restart
Program Protection Settings Break/Make (Auto Retry)
Enables/Disables the ability of the drive to start into a spinning motor when the
ST-to-CC connection momentarily opens and is then closed (Break/Make ST)
or after a power interruption (momentary power failure).
Settings:
Off
Power Failure
Make/Break ST
Both
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Command Mode
Program Utilities Command and Frequency Settings Command
Mode Select
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc.
Settings:
(Use) (Control Terminal Strip) Terminal Block
(Use) LED Keypad
(Use) Common Serial (TTL)
(Use) RS232/RS485
(Use) Communication Card
Parameter Type — Selection List
Factory Default — Terminal Block
Changeable During Run — No
Commercial (Power) Hold Time
Program Special Control Commercial Hold Time
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.
Parameter Type — Selection List
Factory Default — 2.00
Changeable During Run — No
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Brake Fault Internal Timer Commercial (Power) Hold Time