Toshiba W7 Computer Drive User Manual


 
74 W7 ASD Installation and Operation Manual
FP Terminal Assignment
Program Terminal Settings Output Terminals FP FP Terminal
Assignment
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at
65
±5 . 0 µS.
Possible assignments for this output terminal are listed in Table 8 on page 142.
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Adjustment
Program Terminal Settings Output Terminals FP FP Terminal
Adjustment
This parameter sets the full-scale reading of the FP terminal. The full-scale
reading of the monitored variable selected in FP Terminal Setting may be set
here.
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Frequency Command Panel
Program System Information and Setup PID Setup Frequency
Command Panel
While operating using PID control, this parameter sets the reference frequency.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Frequency Display Resolution
Program Utilities Display Attributes Frequency Display
Resolution
The parameter sets the number of decimal places to be displayed during non-
Accel/Decel functions.
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 1
Maximum — 0.01
FM Terminal Assignment Frequency Display Resolution