Toshiba W7 Computer Drive User Manual


 
W7 ASD Installation and Operation Manual 103
Preset Speed #13
Program Preset Speeds 13
This parameter assigns an output frequency to binary number 1101 and is
identified as Preset Speed #13. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #14
Program Preset Speeds 14
This parameter assigns an output frequency to binary number 1110 and is
identified as Preset Speed #14. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #15
Program Preset Speeds 15
This parameter assigns an output frequency to binary number 1111 and is
identified as Preset Speed #15. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
Preset Speed #1 for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed Mode Control
Program Preset Speeds Mode
Enables/Disables the use of the Preset Speed Mode control for Preset Speeds
115.
The Preset Speed Mode control setting determines if the Speed setting only is
used (disabled) or if the user-set combinations of the Torque, Speed, Accel/
Decel, and Direction settings will be used (enabled) while running Preset
Speeds 115.
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Proportional (P) Gain
Program Feedback Settings Proportional Gain
This parameter determines the degree that the Proportional function affects the
output signal when using PID feedback to control the ASD output. The larger
the value entered here, the quicker the ASD responds to changes in feedback.
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.0
Preset Speed #13 Proportional (P) Gain