Xantrex Technology XTR 850 Watt Power Supply User Manual


 
A-20 975-0200-01-01
SCPI Command Reference
Calibrate the
Resistive
controlled
Non Isolated
Voltage APG
feature
[:]CALibration[<channel>]:OUTPut
:ANALog[:VOLTage]:RESistive
Calibrate the Resistive
controlled voltage analog
programming system.
? | <NR1> |
<nothing for
interactive mode>
Yes
Calibrate the
Resistive
controlled
Isolated
Voltage APG
feature
[:]CALibration[<channel>]:OUTPut
:ANALog[:VOLTage] :RESistive:ISOLated
Calibrates the Resistive
controlled voltage analog
programming system.
? | <NR1> |
<nothing for
interactive mode>
Yes
Calibrate the
Resistive
controlled
Non Isolated
Current APG
feature
[:]CALibration[<channel>]:OUTPut
:ANALog:CURRent:RESistive
Calibrate the Resistive
controlled current analog
programming system.
? | <NR1> |
<nothing for
interactive mode>
Yes
Calibrate the
Resistive
controlled
Isolated
Current APG
feature
[:]CALibration[<channel>]:OUTPut
:ANALog:CURRent:RESistive:ISOLated
Calibrates the Resistive
controlled current analog
programming system.
? | <NR1> |
<nothing for
interactive mode>
Yes
Get Ouput
Calibration
Parameters
[:]CALibration[<channel>]:PARameter
[:OUTPut]
Queries and loads the output
calibration parameters in
arbitrary program block data
format.
?|<arbitrary
program block
data>
Yes
Get Analog
Programming
Calibration
Parameters
[:]CALibration[<channel>]:PARameter
:APRogram
Queries and loads the APG
calibration parameters in
arbitrary program block data
format.
?|<arbitray program
block data>
Yes
Table A-4
SCPI Commands for Calibration (Continued)