975-0200-01-01 C-5
Electrical Specifications for XTR 1700 Watt
C
4.From 85–132 Vac or 170–265 Vac, constant load.
5.From 85–132 Vac or 170–265 Vac, constant load.
6.From no load to full load, constant input voltage.
7.For load voltage change, equal to the unit voltage rating, constant input voltage.
8.For 6 V models the ripple is measured at 2–6 V output voltage and full output current. For other models, the ripple is measured at 10–100% output voltage and full output current.
9.When using remote sense, the total of the load voltage and the load line drops must not exceed the rated output of the power supply. For example, for an XTR 6-220 in an application
with 1
V of load line loss (0.5 V/Line), the maximum available load voltage would be 6–1= 5 V. Note: The unit may operate at higher output voltages than this, but there is no guar-
antee that the power supply will meet performance specifications. Ultimately, the upper limit of the output voltage will be determined by internal circuitry of the power supply (non-
adjustable.)
10.With rated, resistive load.
11.At 100/200 Vac input voltage and maximum output power.
Applies to all footnotes: Programming and Readback: RS-232, RS-485, USB built in. GPIB, Ethernet optional.
Specifications are guaranteed from 1% to 100% of the rated output voltage, current, and power.
AC Line Input Specifications for XTR 1700 Watt
The input to the power supply requires the following input specifications.
Rated AC Input Voltage/Frequency 100–240 Vac, 50–60 Hz
Operational AC Input Voltage/Frequency 85–265 Vac continuous, 47–63 Hz, single phase
Input Current (at 100/200 Vac) 23/12 A
Inrush Current (100/200 Vac) Less than 50 A
Power Factor Correction 0.99@100/200 Vac, rated output power