Xerox 4890 IPS Printer User Manual


 
XEROX DOCUPRINT 4850/4890 IPS INSTALLATION PLANNING GUIDE 6-1
6. 6Printer specifications and
requirements
This chapter provides power and space requirements for your
4850/4890 printer. It also provides printer environmental
specifications.
For facts about controller power and space requirements, refer to the
Controller specifications and requirements chapter of this guide.
Power requirements
Your DocuPrint system has important power requirements that must
be accommodated. These requirements are summarized in the table
below. For further details on power requirements, refer to the voltage
charts and wiring diagrams that follow.
For details on controller power requirements, refer to the Controller
specifications and requirements chapter of this guide.
Agency certification: UL 478 and 1950, IEC 950, CSA 22.2 #220-
1986, FCC (Class A), and VDE 0871 (Class A).
Table 6-1. 4850 printer 60 Hz electrical requirements
Voltage Amp. service KVA rating NEMA
120/208 or 120/240 VAC 30 amp Operating: 4.1
Standby: 2.7
14-30R
Table 6-2. 4850 printer 50 Hz DELTA electrical requirements
Voltage Amp. service KVA rating
220, 230, 240 VAC
(3 phase, 4 wire or
single-phase)
30 amp Operating: 3.8
Standby: 2.5
Table 6-3. 4890 printer 60 Hz electrical requirements
Voltage Amp. service KVA rating NEMA
120/208 or 120/240 VAC 30 amp Operating: 5.5 14-30R
Table 6-4. 4890 printer 50 Hz DELTA electrical requirements
Voltage Amp. service KVA rating
220, 230, 240 VAC 30 amp Operating: 5.5