Lantronix 900-371 Network Router User Manual


 
3: Operations
JaneDoe may access the following outlets and groups: outlet A1 which has a
descriptive name of DataServer_1, outlet A2 which has a descriptive name of
WebServer_1, group ServerGroup_1, group ServerGroup_2, and Console serial port.
Outlet Administration
Setting the sequencing interval
The Set Outlet SeqInterval command sets the power on sequencing interval for all
outlets.
To set the sequencing interval:
1. At the SLP prompt, type set outlet interval for all, followed by a
value from 0 to 15 (in seconds) and press Enter.
Setting the reboot delay
The Set Outlet RebootDelay command sets the reboot delay for all outlets.
To set the sequencing interval:
2. At the SLP prompt, type set outlet rebootdelay all, followed by a value
from 5 to 60 (in seconds) and press Enter.
Creating a descriptive outlet name
The Set Outlet Name command assigns a descriptive name to an outlet. You may
use this name in commands that require an outlet name as an alternative to using the
outlet’s absolute name.
To create an outlet name:
1. At the SLP prompt, type set outlet name, followed by the absolute outlet
name, then a descriptive name of up to 24 alphanumeric and other typeable
characters-(ASCII 33 to 126 decimal) are allowed; spaces are not allowed; outlet
names are not case sensitive. Press Enter.
Example
The following command adds the descriptive name Data Server_1 to outlet .a1:
SLP: set outlet name .a1 DataServer_1<Enter>
Setting the outlet wakeup state
The Set Outlet Wakeup command sets the default wakeup state for that outlet. In the
event of a system-wide power loss, this state will be applied to the outlet when power
is restored.
The wakeup state may be set to On, Off or Last. Upon restoration of system power; If
set to ON, the SLP will apply power to that outlet. If set to Off, the SLP will not apply
power to that outlet. If set to Last, the SLP will apply the last known power state.
To set the wakeup state:
1. At the SLP prompt, type set outlet wakeup, followed by on, off or last and
the outlet name. Press Enter.
SecureLinx SLP Remote Power Manager 46