3: Operations
Example
The following command sets the wakeup state for outlet .a1 to off:
SLP: set outlet wakeup off .a1<Enter>
Setting the outlet Post-On delay
The Set Outlet PostOnDelay command sets the Post-On delay for an outlet. This
feature allows and administrator to manage boot dependencies during power-on
sequencing or group commands by delaying the sequencing of subsequent outlets
after an outlet has been powered on.
Note: This delay is applied in addition to the general sequencing interval.
To set the Post-On delay:
2. At the SLP prompt, type set outlet postondelay, followed by a value from
0 to 900 (in seconds) and press Enter.
Example
The following command sets the Post-On delay for outlet .a5 to 90 seconds:
SLP: set outlet postondelay .a5 90<Enter>
Displaying outlet information
The Show Outlets command displays information about all outlets. This information
includes:
• Sequencing and reboot timer values
• Descriptive outlet name, if applicable
• Outlet wakeup state and Post-On settings
To display outlet information:
3. At the SLP prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
SecureLinx SLP Remote Power Manager 47