1.8 Parallel Connected UPS Units
For installations with redundant units, take into account only the units required to supply the load power (e.g. for an
installation made up of 3 parallel-connected UPS units, one being redundant, only 2 UPS units are used to
determine bypass AC source and load currents and cable cross-sections).
Table 1-5 serves as an example for a parallel connected installation comprising up to four UPS units.
Table 1-5: Parameters for Bypass AC Source and Load Cables for a Parallel UPS.
Parameters
rated unit number of total UPS bypass AC
output parallel- rated output source or load
in kVA connected in kVA line current
units in Amps
100 2 200 240
3 300 360
4 400 480
130 2 260 312
3 390 468
4 520 624
150 2 300 360
3 450 540
4 600 720
180 2 360 434
3 540 651
4 720 868
200 2 400 482
3 600 723
4 800 964
225 2 450 542
3 675 813
4 900 1084