2.1 Receiving
On delivery, check that the equipment has not been damaged in transport (declare any damage to the carrier in
accordance with customary claim procedures).
Also check that the characteristics noted in the test report for the equipment correspond to those specified on the
order form. In the event of a non-conforming item, quote the delivery note reference number when making your
claim.
2.1.1 Handling
The cabinets are delivered on pallets, equipped with a shock absorbing system. Ideally, the equipment should be
unpacked just before installation (see "unpacking" section below). Cabinet weights and dimensions are specified on
the packaging. Cabinets may be handled in one of the following ways (see Figure 2-1):
Rolling on Bars (B)
Do not mount the foot pads, but place the cabinet on the rollers (at least three). The cabinet may be pulled on rollers
using a sling positioned horizontally. This technique should only be used when absolutely necessary (narrow
doorway or corridor, preventing the use of a fork-lift or pallet-mover).
From the Bottom (A)
The cabinets can be moved from the front or the rear (715 mm wide cabinets) using a pallet truck or fork-lift truck,
or on the 4 surfaces (1015 mm and 1215 mm wide cabinets) using a fork-lift truck.
Fork tunnel height: 140 ±10 mm.
Fork opening: 560, 650 or 700 mm according to cabinets width.
The 715 mm wide cabinets are designed to pass through 715 mm wide openings, and the other cabinets are
designed to pass through 825 mm wide openings. For narrow openings, (follow the instructions below) cabinets are
normally 825 mm deep.
This depth can be reduced to:
817 mm by removing rear panels.
805 mm by removing doors.
800 mm by removing doors and door hinges.
unpack the cabinet, refer to section 2.2 ‘Unpacking’, page 4. The cabinet can then be handled by lifting machines
on all surfaces after the pallets have been dismantled by removing the rear panels, and remove the fixing screws
using a "torx" screwdriver.
Removing the doors:
1. Open the door(s).
2. Disconnect the door earth connection from the frame.
3. For cabinets fitted with a control panel, carefully disconnect the ribbon cables from the panel circuit boards
located on the inside of the door.
4. Knock out the hinge pins from below.
5. Remove the door(s).
Removing the door hinges:
1. Remove the screws holding the side panels to the hinges.
2. Remove the central screw holding the hinge.
Galaxy PWUPS 100 to 225kVA