Schneider Electric 58 TRX Computer Drive User Manual


 
Altivar
®
58 TRX AC Drives
Wiring Recommendations
© 2000–2003 Schneider Electric All Rights Reserved
104
09/2003
The ATV58AHD28N4 is rated for 8 kHz operation at 25 HP.
Note: Shaded items in the table indicate 30,000 AIC.
Ratings for Input Line Currents, Type H Variable Torque 400/460 Vac
Three-Phase Input with Three-Phase Output
Switching Frequency: ATV58HU18 to D23 at 8 kHz, ATV58HU28N4 to D46N4 at 4 kHz,
ATV58HD54N4 to C33N4X at 2 kHz
Drive Controller
Catalog Number
Motor Power
Rated
Output
Current
In
Input Line Current
5000 AIC 10000 AIC 22000 AIC
w/ Additional 3%
Line Impedance
22000 AIC
400 V
kW
460 V
HP
A
400 V
A
460 V
A
400 V
A
460 V
A
400 V
A
460 V
A
400 V
A
460 V
A
ATV58HU18N4• 0.75 1 2.1 3.2 2.8 1.9 1.6
ATV58HU29N4• 1.5 2 3.4 5.5 4.8 3.3 3
ATV58HU54N4• 3 4 6.2 10.2 7.8 6.3 5.6
ATV58HU72N4• 4 5 7.6 12.2 10.7 8.6 7.2
ATV58HU90N4• 5.5 7.5 11 16.3 14.3 11.8 10.1
ATV58HD12N4• 7.5 10 14 20.7 18.2 22.7 19.9 26.5 21 16 13.2
ATV58HD16N4• 11 15 21 28.8 25.3 31.4 27.6 35.4 28 23.6 19.5
ATV58HD23N4• 15 20 27 36.5 32 39.6 34.7 44.7 35.6 30.6 25.8
ATV58HD28N4•
18.5 25 34 36.3 32.7 36.9 33.4 37.4 34.1 37.6 34
ATV58HD28N4• 22 30 40 42.3 38.1 43 38.7 43.9 39.8 43.6 39.6
ATV58HD33N4• 30 40 52 55.5 49.3 56.3 51.1 57.1 51.6 56.8 51.4
ATV58HD46N4• 37 50 65 68.9 61.8 70.9 63.5 72.3 65.4 72 65.1
ATV58HD54N4• 45 60 77 82.7 72.3 84.1 75.2 85.5 77.7 85.5 77.5
ATV58HD64N4• 55 75 96 103.7 91 107 96.3 111.1 100.8 111.1 100
ATV58HD79N4• 75 100 124 133.6 117.4 138 122.6 142.9 129.3 142.4 128.8
ATV58HC10N4X 90 125 156 129 161 144 180 159 176
ATV58HC13N4X 110 150 180 147 184 165 206 182 202
ATV58HC15N4X 132 200 240 185 232 212 265 234 260
ATV58HC19N4X 160 250 302 260 325 288 320
ATV58HC23N4X 200 300 361 300 373 329 366
ATV58HC25N4X 220 350 414 337 422 372 413
ATV58HC28N4X 250 400 477 375 468 414 460
ATV58HC31N4X 280 450 515
415 519 458 508
ATV58HC33N4X 315 500 590
455 569 502 557
Ratings for Input Line Currents, Types E and F 200 Vac -10% / 240 Vac +10%
Single-Phase Input with Three-Phase Output
Drive Controller
Catalog Number
Motor Power at 4 kHz
Switching Frequency
Rated
Output
Current (In)
Input Line Current
2000 AIC 5000 AIC
with Additional 3%
Line Impedance
kW HP A
200 V
A
240 V
A
200 V
A
240 V
A
200 V
A
240 V
A
ATV58EU09M2ZU 0.37 0.5 2.3 5.6 4.7 4.2 3.8
ATV58EU18M2ZU 0.75 1 4.1 9.8 8.3 7.9 7
ATV58EU29M2ZU 1.5 2 7.8 18.5 15.6 14.1 12.3
ATV58EU41M2ZU 2.2 3 11 25.6 21.6 20.5 17.5
NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.