Altivar
®
58 TRX AC Drives
Communication Parameters
© 2000–2003 Schneider Electric All Rights Reserved
82
09/2003
W113
or
16#5FE2/E
AO1 Assignment of
analog output
AO1
(Only on ATV58
Type FVC drive
controllers)
0 = NO: Not assigned
1 = OCR: Motor current
2 = OFR: Motor speed
3 = ORP: Ramp output
4 = TRQ: Motor torque
5 = STQ: Signed motor torque
6 = ORS: Signed ramp output
7 = OPS: PID reference
8 = OPF: PID feedback
9 = OPE: PID error
10 = OPI: PID integral
11 = OPR: Motor power output
12 = THR: Motor thermal state
13 = THD: Drive thermal state
Fault Configuration Registers
Word Code Description Possible Values or Range
W150
or 16#5FE3/1
ATR — Automatic restart
W151
or 16#5FE3/2
OPL — Motor phase loss
W152
or 16#5FE3/3
IPL — Input phase loss
W153
or 16#5FE3/4
THT — Motor thermal protection
W154
or 16#5FE3/5
LFL — Loss of follower
W155
or 16#5FE3/6
FLR — Catch a spinning load
W156
or 16#5FE3/7
STP — Controlled stop on loss of input power
W157
or 16#5FE3/8
SDD — Ramp not followed
W158
or 16#5FE3/9
RST — Type of reset
W159
or 16#5FE3/A
LFF 0.1 Hz Default speed if 4–20 mA follower signal is lost.
W160
or 16#5FE3/B
EPL Response to external fault input issued by logic
input
1 = Yes: Immediate fault
3 = LSF: Stop followed by fault indiction
W161
or 16#5FE3/C
ACB Electronic output phase inversion 0 = No
1 = Yes
Adjustment Registers
Word Code Units Description Possible Values or Range
W250
or 16#5FE5/1
HSP 0.1 Hz High speed LSP to TFR
W251
or 16#5FE5/2
LSP 0.1 Hz Low speed 0 to HSP
W252
or 16#5FE5/3
ACC 0.1 s
or
0.01 s
Acceleration
(time between 0 and FRS)
0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for TypeFVC.
W253
or 16#5FE5/4
DEC 0.1 s
or
0.01 s
Deceleration
(time between FRS and 0)
0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for TypeFVC.
W254
or 16#5FE5/5
UFR 1% IR compensation
(adjustment of auto-tune value)
0 to 150 if SPC = No
0 to 800 if SPC = Yes
0 if CFG = VT
W255
or 16#5FE5/6
FLG 1% Frequency loop gain 0 to 100
W256
[1]
or 16#5FE5/7
PFL 1% V/F ratio profile 0 to 100 if CFG = VT
100 if CFG = HDG or GEN
W257
or 16#5FE5/8
STA 1% Frequency loop stability 0 to 100
W258
or 16#5FE5/9
ITH 0.1 A Current setting for motor thermal protection 0.25 to 1.36
x INV (drive controller nominal current)
W259
or 16#5FE5/A
SLP 1% Slip compensation 0 if CFG = VT
0 to 150 if CFG = HDG or GEN
W260
or 16#5FE5/B
AC2 0.1 s
or
0.01 s
Acceleration 2
(time between 0 and FRS)
0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for TypeFVC.
W261
or 16#5FE5/C
DE2 0.1 s
or
0.01 s
Deceleration 2
(time between FRS and 0)
0: ramp of 0.05 s (special case)
1 to 9999: ramp of 0.1 s to 999.9 s or
0.01 to 99.99. See INR (W291) for TypeFVC.
[1]
This parameter does not exist for ATV58 Type FVC drive controllers.
I/O Configuration Registers (Continued)
Word Code Description Possible Values or Range
[1]
Values specific to ATV58 Type FVC models