Schneider Electric 58 TRX Computer Drive User Manual


 
Class 8839 58M Enclosed AC Drives
Dimensions and Weights for Mounting
166
09/2003
© 2000–2003 Schneider Electric All Rights Reserved
Class 8839 58M Enclosed Drives: Barriered 25–75 hp CT Controllers and 30–100 hp VT
Controllers @ 460 V and 15–40/50 hp CT/VT Controllers @ 208/230 V
D
E
F
B
Ø1.50
(38.1)
Lifting
Holes
20.38
(517.7)
5.90
(149.9)
A
G
C
Ø0.625
(15.875)
1.00
(25.4)
Conduit Entry - Top View
Conduit Entry - Bottom View
14.00
(355.6)
3.00
(76.2)
H
42.0
(1066.8)
42.0
(1066.8)
C
L
NOTE: Remove plenum fan filter, front
grill, and retaining bracket assembly to
access the mounting hole locations.
NOTE: Provide at least 36 in. of
mounting clearance in front of the drive
controller and at least 24 in. of mounting
clearance at the top of the drive
controller. Floor-mounted units may be
mounted side by side without
clearance.
NOTE: Remove the top or bottom
conduit plates as necessary to facilitate
the appropriate conduit entry. Ensure
that the plates are replaced before
working on the drive controller.
hp Weight Enclosure Dimensions
Enclosure
Size
460 V 208/230 V A B C D E F G H
CT VT CT VT lb kg in. mm in. mm in. mm in. mm in. mm in.
m
m
in. mm In. mm
25–40 30–50 15–20 15–25 398 181 83.38 2117.9 93.87 2384.3 84 2133.6 23.75 603.3 19 482.6 25 635 8.0 203.2 23 584.2 E-barriered
50–75 60–100 25–40 30–50 590 268 83.38 2117.9 93.87 2384.3 84 2133.6 25.75 654.1 24 609.6 30 762 8.0 203.2 28 711.2 F-barriered
barriered E,F dims.eps