Schneider Electric 58 TRX Computer Drive User Manual


 
Class 8998 Motor Control Centers
AC Drive Options and Basic Drive Power Circuit
214
09/2003
© 2000–2003 Schneider Electric All Rights Reserved
Keypad frequency reference (in Hz).
Output power (as a percentage of drive rated power).
Energy consumed (in kilowatts).
Run time (in hours).
One normally-open contact indication of drive running (closes on run).
One normally-closed contact indication of drive fault (opens on fault).
Optional analog output for motor current, motor frequency, ramp output, motor power, and motor torque.
AC DRIVE OPTIONS
Commissioning software for personal computers.
24 Vdc analog I/O extension card (tachometer feedback).
24 Vdc digital I/O extension card (encoder feedback).
Modbus
®
plus communication card.
Unitelway/Modbus communication card.
Profibus DP communication card.
Ethernet communication card for Transparent Ready™ integration.
DeviceNet communication card.
BASIC “DRIVE” POWER CIRCUIT
Consists of disconnect switch and drive pre-programmed for selected options if applicable.
Includes current-limiting power fuses, if necessary. Power fuses are UL Class J.
Unit is UL 845 Listed for 100,000 amperes Short Circuit Current.
Includes operation keypad/display mounted on front of the unit.
Pilot devices are optional and are only available as 22 mm Telemecanique type pilot devices (five
devices maximum).
Control power transformer (480 V/120 V), if necessary, for enclosure ventilation fans is included.
M
CB or Disc
Power
Fuse
Drive
8998-003.art
Basic “Drive”
Power Circuit