Altivar
®
58 TRX AC Drives
Type E Drive Controllers
© 2000–2003 Schneider Electric All Rights Reserved
12
09/2003
ATV58 TRX TYPE E DRIVE CONTROLLERS
The ATV58 TRX family of adjustable-frequency AC drive controllers is used
to control three-phase asynchronous motors. The ATV58 TRX Type E model
contains an ATV58 TRX Type H drive controller packaged in a compact, Type
1 enclosure. It is for use in mechanical rooms, OEM equipment, and factory
floor applications. The following Type E drive controller models are available:
• 1 to 7½ hp (0.75 to 5.5 kW), 400/460 Vac, three-phase input
• ½ to 3 hp (0.37 to 2.2 kW), 200/240 Vac, single-phase input
• 2 to 3 hp (1.5 to 2.2 kW), 200/240 Vac, three-phase input
Each ATV58 TRX Type E drive controller contains:
• A GV2 manual motor starter, ATV58 TRX drive controller, and an output
contactor
• A three-position selector switch wired for “RUN FORWARD”
• A manual speed potentiometer mounted on the front of the enclosure
• Space for two additional 16-mm operators
• Four conduit openings that are closed with plugs
• A transparent plastic door for viewing the status LEDs and a separately-
supplied keypad
All ATV58 TRX communication and I/O options can be used in the Type E
controllers. The Type E drive controllers can be used on constant or variable
torque applications. The ratings are shown in the tables below.
200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, Single-Phase Input with 3-Phase Output
Frame
Size
▲
Drive Controller
Catalog Number
Motor Power
▼
Rated
Output Current
Transient
Output Current
◆
kW HP A A
1 ATV58EU09M2ZU 0.37 0.5 2.3 3.1
1 ATV58EU18M2ZU 0.75 1 4.1 5.6
2 ATV58EU29M2ZU 1.5 2 7.8 10.6
3 ATV58EU41M2ZU
■
2.2 3 11 15
200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output
Frame
Size
▲
Drive Controller
Catalog Number
Motor Power
▼
Rated
Output Current
Transient
Output Current
◆
kW HP A A
2 ATV58EU29M2ZU 1.5 2 7.8 10.6
3 ATV58EU41M2ZU 2.2 3 11 15
400 Vac -10% / 460 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output
Frame
Size
▲
Drive Controller
Catalog Number
Motor Power
▼
Rated
Output Current
Transient
Output Current
◆
kW HP A A
2 ATV58EU18N4ZU 0.75 1 2.3 3.1
2 ATV58EU29N4ZU 1.5 2 4.1 5.6
2 ATV58EU41N4ZU 2.2 3 5.8 7.9
3 ATV58EU54N4ZU 3 – 7.8 10.6
3 ATV58EU72N4ZU 4 5 10.5 14.3
3 ATV58EU90N4ZU 5.5 7.5 13 17.7
▲ For dimensions, see page 122; for wiring diagrams, see pages 109 and 110.
▼ Power indicated is for a switching frequency between 0.5 and 4 kHz, and at steady state. For switching
frequency between 8 and 16 kHz, use the next largest size drive controller. (For example, for 2 hp, order drive
controller ATV58EU41M2ZU.) If the duty cycle (that is, the drive controller run time) does not exceed 60% (36
second maximum for a 60 second cycle), this is not necessary.
◆ For 60 seconds.
■ A line reactor (3% minimum) must be used with this drive controller.
ATV58 TRX Type E Product Family
ATV58NEMAb_w no back.tif