Class 8839 Econoflex™ AC Drives
Ratings
196
09/2003
© 2000–2003 Schneider Electric All Rights Reserved
INPUT CURRENT RATINGS (CONTINUED)
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 230 Vac
▲
Drive Controller
Catalog Number
▼
Motor Power
230 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
■
Mod A09
5 kAIC (0.141 mH)
(A)
22 kAIC (0.032 mH)
(A)
58EC•3V_ 1 4.9 5.6 3.3 3.5
58ED•3V_ 2 8.6 9.7 5.6 5.9
58EE•3V_ 3 11.8 13.4 8.1 8.5
58EF•3V_ 5 19.5 22.1 14.1 14.7
58EG•3V_ 7.5 26.4 30 19.9 20.6
58EH•3V_ 10 35 38.2 27.5 28.6
58EJ•3V_ 15 37.8 38 37.8 38
58EK•3V_ 20 50.5 50.8 50.5 50.8
58EL•3V_ 25 61.8 61.8 61.8 61.8
58EM•3V_ 30 73.3 73.6 73.3 73.6
58EN•3V_ 40 97.9 98.5 97.9 98.5
58EP•3V_ 50 121.2 124 121.2 124
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 208 Vac
▲
Drive Controller
Catalog Number
▼
Motor Power
208 Vac 60 Hz
(HP)
5 kAIC
(0.141 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
■
Mod A09
5 kAIC (0.141 mH)
(A)
22 kAIC (0.032 mH)
(A)
58EC•2V_ 1 5.3 6 3.7 3.8
58ED•2V_ 2 9.4 10.6 6.5 6.6
58EE•2V_ 3 13 14.5 9.2 9.5
58EF•2V_ 5 21.4 24 16.2 17.1
58EG•2V_ 7.5 29 34.7 22.9 23.3
58EH•2V_ 10 38.3 44.4 31.7 32.3
58EJ•2V_ 15 41.7 41.7 41.7 41.7
58EK•2V_ 20 55.5 55.7 55.5 55.7
58EL•2V_ 25 67 67.2 67 67.2
58EM•2V_ 30 80.9 80.9 80.9 80.9
58EN•2V_ 40 107.6 108.4 107.6 108.4
58EP•2V_ 50 134.8 135.5 134.8 135.5
▲ Select conductor based on the input line current.
▼ The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
■ Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.