Ratings for Input Line Currents, Type N 208 to 230 Vac
Single-Phase Input with Three-Phase Output / Three-Phase Input with Three-Phase Output
Ratings for Input Line Currents, Types E and F 200 Vac -10% / 240 Vac +10%
Three-Phase Input with Three-Phase Output
Drive Controller
Catalog Number
Motor Power at 4 kHz
Switching Frequency
Rated
Output
Current (In)
Input Line Current
5000 AIC
with Additional 3%
Line Impedance
kW HP A
200 V
A
240 V
A
200 V
A
240 V
A
ATV58EU29M2ZU 1.5 2 7.8 9.7 8.3 6.6 5.9
ATV58EU41M2ZU 2.2 3 11 13.4 11.4 9.5 8.5
Ratings for Input Line Currents, Types E and F 400 Vac -15% / 460 Vac +20%
Three-Phase Input with Three-Phase Output
Drive Controller
Catalog Number
Motor Power at 4 kHz
Switching Frequency
Rated
Output
Current
(In)
Input Line Current
5000 AIC
with Additional 3%
Line Impedance
400 V
kW
460 V
HP
A
400 V
A
460 V
A
400 V
A
460 V
A
ATV58EU18N4ZU 0.75 1 2.3 3.4 2.6 1.9 1.6
ATV58EU29N4ZU 1.5 2 4.1 6 4.5 3.3 3
ATV58EU41N4ZU 2.2 3 5.8 7.8 6 4.8 4.2
ATV58EU54N4ZU 3 7.8 10.2 7.8 6.3 5.6
ATV58EU72N4ZU 4 5 10.5 13 10.1 8.6 7.2
ATV58EU90N4ZU 5.5 7.5 13 17 13.2 11.8 10.1
208 to 230 Vac, Single-Phase Input with 3-Phase Output
Drive Controller Catalog Number
Dissipated Power at Rated
Load (Total)
Short Circuit Rating Input Line Current
WA RMS sym.AA
ATV58NU09M2• 42 2,000 5.6 4.7
ATV58NU18M2• 64 2,000 9.8 8.3
ATV58NU29M2• 107 5,000 18.5 15.6
ATV58NU41M2•
160 5,000 25.6 21.6
When these drive controllers are used with a single-phase input, a line reactor (3% minimum) must be used.
208 to 230 Vac, 3-Phase Input with 3-Phase Output
Drive Controller Catalog Number
Dissipated Power at Rated
Load (Total)
Short Circuit Rating Input Line Current
WA RMS sym.AA
ATV58NU29M2• 107 5,000 9.7 8.3
ATV58NU41M2• 160 5,000 13.4 11.4
ATV58NU54M2• 190 5,000 17.2 15
ATV58NU72M2• 240 5,000 22.4 19.5
NOTE: The input
conductor ampacity
rating should not be
less than the
ampacity rating
selected based on the
rated controller output
current.