Class 8839 58M Enclosed AC Drives
Three Phase Line Reactors
160
09/2003
© 2000–2003 Schneider Electric All Rights Reserved
The Class 8839 58M Enclosed AC Drives are
designed to operate from industrial power systems
with normal AC line conditions without the need of
additional line impedance from either an isolation
transformer or a line reactor. However, when
abnormal line conditions exist, additional line
impedance may be required. Typically, line reactors
are used to:
• Reduce the input rms current to the AC drive
ratings
• Lower the available fault current on high fault
distribution systems
• Limit the total harmonic voltage distortion from
the AC drive at the point of common coupling to
align with IEEE 519 guidelines
• Prevent AC drive nuisance tripping due to
transient overvoltages from power factor
correction capacitor switching
Line Reactors:
1. The line reactors are manufactured by
MTE, Inc.
2. Harmonic compensated up to 150% of
nominal current ratings
3. 5% nominal reactance
4. Refer to the following publications on the
subject of harmonics and benefits of drive
isolation transformers:
— 8803PD9402–Power Systems Harmonics–
Cause and Effects of AC Drives.
— 7460HO9501–Drive Isolation
Transformers-Application, Selection and
Specification Data
— 7460PD9501– Drive Isolation
Transformers–Solutions to Power Quality
HP Rating
208/230 VAC Line Reactor
Part No. (Integrated)
460 VAC Line Reactor
Part No. (Integrated)
Enclosed Standard Option
1 RL–01202 RL–00802 A10
2 RL–01202 RL–00802 A10
3 RL–01202 RL–00802 A10
5 RL–01801 RL–01203 A10
7.5 RL–01801 RL–01203 A10
10 RL–03501 RL–01802 A10
15 RL–03501 RL–01802 A10
20 RL–08001 RL–01802 A10
25 RL–08001 RL–03502 A10
30 RL–10001 RL–03502 A10
40 RL–10001 RL–03502 A10
50 RL–16002 RL–08002 A10
60 – RL–08002 A10
75 – RL–10002 A10
100 – RL–13002 A10
125 – RL–16013 A10
150 – RL–20013 A10
200 – RL–25013 A10
250 – RL–32013 A10
300 – RL–40013 A10
350 – RL–50013 A10
400 – RL–50013 A10
450 – RL-60013 A10
500 – RL-60013 A10
LoadLine
A1
B1
C1
A2
B2
C2
LineLoad.eps