Schneider Electric 58 TRX Computer Drive User Manual


 
Altivar
®
58 TRX AC Drives
I/O Extension Cards
31
09/2003
© 2000–2003 Schneider Electric All Rights Reserved
AO1
COM
AI1
+10V
AI2
LI1
LI2
LI3
LI4
+24V
SW1
SW2
SW3
SW4
AO1 COM AI1 +10V AI2 ACI1 ACI2 ACI3 ACI4 ACCOM
115 V
~
Top of the logic
input module
Control terminal strip
Module
terminal block
NOTE: 115 Vac is
present at these five
terminals.
DC control wiring
AC control wiring
input wiring.eps
115 Vac Logic Input Module Typical Wiring
115 VAC Logic Input Module (VW3A58275U)
The 115 Vac logic input module, catalog number VW3A58275U, makes it
possible to use ATV58 TRX control terminal points LI1, LI2, LI3, and LI4 with
control circuits that require 115 Vac control. The module insolates the
115 Vac signals from the 24 Vdc input signals of the drive controller terminal
strip, without modifying the other signals.
The 115 Vac logic input module is designed for use only on the Type H and
Type N families of ATV58 TRX drive controllers. It requires no special
programming.
Drive controller logic inputs LI1, LI2, LI3, and LI4 retain their functionality
when using this module. These inputs correspond to the module inputs
labeled ACI1, ACI2, ACI3, and ACI4 respectively.
The figure at the left shows typical wiring using four switches, operating on
115 Vac, as inputs to the drive controller. Power is derived from a 115 Vac
power source wired to the switches, then to inputs ACI1–ACI4. The 115 Vac
common must be connected to the ACCOM terminal on the module.
See the table below for electrical specifications. The module accepts
26–16 AWG (0.14–1.3 mm
2
) wire.
ACI1
ACI2
ACI3
ACI4
Frequency 47 to 63 Hz
Input Impedance 28 kΩ ±10% @ 25 °C (77 °F)
Maximum Allowable
Voltage Range
0–132 Vrms
Input to Guarantee On
State
90 to 132 Vrms
Input to Guarantee Off
State
a
a. Coupling can cause voltages higher than 50 Vrms, which can turn the
input on or prevent it from turning off.
0 to 50 Vrms
Storage Temperature -25 to 70 °C (-13 to 158 °F)