The following table describes the functions and characteristics of the pump
switching option card control terminals.
NOTE: There is no +24 Vdc power supply output on this option card;
therefore, it is necessary to connect an external +24 Vdc power source
between terminals DO+ (+) and COMDI (-).
Function Characteristics
Available DC Power Supplies
+10 and -10
Protected against short circuits and overloads
2 outputs, +10 Vdc and -10 Vdc
Maximum current = 10 mA each
Digital Logic Inputs
DI5, DI6, DI7
3 reassignable logic inputs. Impedance = 3.5 k. Compatible with
Level 1 PLCs according to IEC 60065A-68. Maximum shielded
cable length: 330 ft (100 m).
Supply: +24 V (11 V min., 30 V max.)
State 0 if < 5 V, state 1 if > 11 V.
The logic inputs are sampled every 2 ms, maximum.
Logic Outputs
DO1, DO2, DO3, DO4
4 reassignable open collector logic output, compatible with Level 1
PLCs according to IEC 60065A-68.
Supply: +24 V (12 V min., 30 V max.),
maximum current = 200 mA each with external source.
The logic output is updated every 2 ms, maximum.
Analog Output
AO
1 reassignable 0
20 mA analog output
Maximum load impedance = 500 .
Resolution: 0.04 mA (9 bits)
Linearity: ± 0.1 mA
Accuracy: ± 0.2 mA
The analog output is updated every 2 ms, maximum.
Analog Input
AI3A, AI3B
1 reassignable, ±10 V bipolar differential input.
Input Impedance: AI3A to AI3B > 300 k.
AI3A to COM 30 k
AI3B to COM > 600 k
Maximum allowable voltage: ± 30 V.
Frequency reference resolution: 0.1 Hz for 100 Hz (0.1% of
maximum frequency), 10 bits plus sign.
Accuracy: ± 0.5%.
Linearity: ± 0.2% of the maximum output frequency.
The analog input is sampled every 2 ms, maximum.
Maximum length of shielded cable: 66 ft (20 m).
COM
0 Vdc
Common for analog input signal
COM DI
0 Vdc
Common for logic inputs, logic outputs, and analog output
External Logic Output Power
DO+
Input: +24 Vdc nominal (12 Vdc min., 30 Vdc max.)
Maximum current = 200 mA per logic output.
[1] Maximum wire size capacity 1.5 mm
2
(AWG 14).
Recommended tightening torque is 3.54 lb-in (0.4 N•m).
COM
AI3A
AI3B
-10
+10
AO
COMDI
DO1
DO2
DO3
DI5
DI6
DI7
DO4
DO+
VW3A58210
Terminals for the
Pump Switching Option Card
Terminal Locations.eps