Schneider Electric SR2MAN01 Webcam User Manual


 
Diagnostics
188
SR2MAN01 11/2007
Smart Relay Messages
Description Here is detailed information on the error messages that are returned by the smart
relay, their possible causes and how to remedy the problem.
Error Messages The table below lists the error messages that a smart relay could return. These
messages generally indicate incompatible actions requested by the user.
Message Cause Corrective action
NO PARAMETER
The user has requested to access the
PARAMETERS option when no parameter is
available (the diagram does not include any
elements with parameters).
TRANSF.ERR.
A transfer was in progress and the link with the
PC was unexpectedly interrupted.
See the documentation for the
programming software.
TRANSFER ERROR: NO
MEMORY
A transfer to the EEPROM was requested and the
EEPROM is not present or incorrectly located.
Check the presence and correct
location of the EEPROM.
TRANSFER ERROR:
CONFIG INCOMPAT
The user has requested to transfer a program
that does not match the characteristics of the
target smart relay, for example: Clock, analog
input, software version.
Check the origin of the program to transfer
and choose a program that is compatible
with the appropriate smart relay.
TRANSFER ERROR:
VERSION. INCOMPAT
This error appears if one of the versions of the
smart relay does not correspond to: Firmware,
LD or FBD functions
Check the firmware version used.
Outputs are displayed
flashing on the main screen
One or more static outputs have shorted or
overloaded.
Troubleshoot, then stop the smart relay
to end the blinking before selecting
RUN mode again (automatic reset).