Apx-2
Appendix B. Specifications
SwitchCard: Up to 16 Modules
Interface: RJ45-3, Three Jacks, 8 Pins Switched Common Jack to A or B Jack.
Contacts: High Reliability, Mechanical Relays, Break-Before-Make Contacts with 1
Amp @ 30 VDC Rating, 100 Million Cycle Life.
Switching:
Manual: Individual Toggle Switch, Gang Switching from Control Module.
Code/WebBrowser: By Slot Number or by Name.
CardRackandControlUnit
EthernetPort: 10/100Base-T
SerialConsolePort: 1 each, RJ45, RS232C
AUXPort: 5-Pin Quick-Connect Terminal Block for External Connection for Alarm
Output, Monitor Input and Ground. Monitor Input Signal is always read relative to
ground signal.
LowMonitorInputSignal: 0V to -48V
HighMonitorInputSignal: +5V to +48V
RS232PortInterface:
Connectors: One (1) RJ45 connector (DTE pinout.)
Coding: 7/8 bits, Even, Odd, No Parity, 1, 2 Stop Bits.
FlowControl: XON/XOFF, RTS/CTS, Both, or None.
DataRate: 300 to 115.2K bps (all standard rates).
InactivityTimeout: No activity timeout disconnects port/modem sessions.
Off, 5, 15, 30, 90 minutes.
Break: Send Break or Inhibit Break
SiteID: 32 Characters.
PortName: 16 Characters per port.
Usernames&Passwords: 32 character usernames; 16 character passwords (case
sensitive.) Up to 128 pairs, definable circuit module, circuit group and
system access.
Physical/Environmental:
Size: 5.25” x 19.00” x 6.75” (H x W x D)
Power: 100/240 VAC 50/60 Hz, 15 watts
Weight: Shipping Weight, Fully Loaded, 15 pounds
OperatingTemperature:32˚Fto122˚F(0˚Cto50˚C)
Humidity: 10 - 90% RH
Venting: Side vents are used to dissipate heat generated within the unit. When
mounting the unit in an equipment rack, make certain to allow adequate
clearance for venting.