Western Telematic AFS-16-1 Switch User Manual


 
7-13
Alarm Configuration
7.6.1.1. Monitor Input Signal - Trigger When Low
To set up the Monitor/Alarm Input feature to trigger an alarm when the signal at AUX
connector pin 4 (the Monitor Input) goes Low, configure the AFS-16 as follows:
1. ControlCardJumperSetting: Set the Jumper to the "1" position (default.) This
will set the non-active, non-alarm signal state to "High" as shown in Figure 7.2.
2. Monitor/AlarmInputLevel: Use the Monitor/Alarm Input configuration menu to
set the Monitor Alarm Input Level to "Low" as described in Section 7.6. This will
configure the Monitor/Alarm Input feature to generate an alarm when the Monitor
Input signal goes Low.
3. SettheRemainingParameters: Use the Monitor/Alarm Input configuration menu
to select the remaining parameters as described in Section 7.6.
4. ConnectMonitorInput: Connect the signal line that you wish to monitor to Pin 4
(Monitor Input) on the Control Module AUX Connector as shown in Figure 7.3.
7.6.1.2. Monitor Input Signal - Trigger When High
To set up the Monitor/Alarm Input feature to trigger an alarm when the signal at AUX
Connector pin 4 (the Monitor Input) goes High, configure the AFS-16 as follows:
1. ControlCardJumperSetting: Set the Jumper to the "0" position. This will set the
non-active, non-alarm signal state to "Low" as shown in Figure 7.2.
2. Monitor/AlarmInputLevel: Use the Monitor/Alarm Input configuration menu to
set the Monitor Alarm Input Level to "High" as described in Section 7.6. This will
configure the Monitor/Alarm Input feature to generate an alarm when the Monitor
Input signal goes High.
3. SettheRemainingParameters: Use the Monitor/Alarm Input configuration menu
to select the remaining parameters as described in Section 7.6.
4. ConnectMonitorInput: Connect the signal line that you wish to monitor to Pin 4
(Monitor Input) on the Control Module AUX Connector as shown in Figure 7.3.
Connect your ground line to the Ground Connector (Pin 5).