Western Telematic AFS-16-1 Switch User Manual


 
7-11
Alarm Configuration
• ContactOutputEnable: Activates/deactivates the Output Contacts on the Control
Module AUX Connector. When the Contact Output Enable parameter is set to
"On", the Common line will be switched from the Normally Closed contact to the
Normally Open contact. For more information on the Output Contacts, please refer
to Section 7.1. (Default = On.)
Note:Ifeitherofthe"CopytoAllTriggers"optionsisselected,thentheContact
OutputEnableparameterforotheralarmswillalsobeenabledordisabledas
specifiedbythisparameter.
• CircuitstoSwitch: Selects the Circuit Module(s) and Circuit Group(s) that will
be switched when the Monitor/Alarm Input feature is triggered, determines the
A/B switch position and enables/disables the "Return" feature. This item provides
access to a submenu which is used to define the following:
Enable: Enables/disables A/B switching in response to the Monitor/Alarm Input
feature. When disabled, the AFS-16 will not perform A/B switching with the
Monitor/Alarm Input feature is triggered. (Default = Disable.)
CircuitState: Specifies the A/B position that circuits will be switched to when
the Monitor/Alarm Input feature is triggered. (Default = B.)
Return: Enables/Disables the Return feature, which allows the AFS-16 to switch
circuits back to their original state after a Monitor/Alarm Input event has been
cleared. (Default = On.)
CircuitAccess: Determines which Circuit Modules will be switched when the
Monitor/Alarm Input feature is triggered. Note that in the Text Interface, Circuit
Access is defined via a separate submenu; in the Web Browser Interface, Circuit
Access is defined via a drop down menu, which is accessed by clicking on the
"plus" sign in the "Configure Circuit Access" field. (Default = undefined.)
CircuitGroupAccess: Determines which Circuit Group(s) the Monitor/Alarm
Input feature will be applied to. Note that in the Text Interface, Circuit Group
Access is defined via a separate submenu; in the Web Browser Interface, Circuit
Group Access is defined via a drop down menu, which is accessed by clicking
on the "plus" sign. (Default = undefined.)