7-10
Alarm Configuration
7.6. Monitor/Alarm Input
The Monitor/Alarm Input feature allows the AFS-16 to monitor Pin 4 on the Control
Module's AUX connector, and then switch circuit modules, and/or activate an audible
alarm or other external device and/or send notification when the signal at Pin 4 changes.
To configure the Monitor/Alarm Input feature, you must access the AFS-16 command
mode using a password that permits Administrator Level commands. The Monitor/
Alarm Input configuration menu offers the following parameters:
• TriggerEnable: Enables/Disables the trigger for this alarm. When Disabled, this
alarm will be suppressed. (Default = On.)
• Monitor/AlarmInputLevel: Determines whether a high or low signal at the
Monitor Input contact (Pin 4 on the Control Module's AUX Connector) will generate
an alarm. For example, if the Monitor/Alarm Input Level is set at "Low", then
an alarm will be triggered when a low signal is detected at Pin 4. Note that the
Monitor/Alarm Input Level is always set to compliment the setting for the Monitor
Input Level Jumper as described in Section 7.5.1. (Default = Low.)
• Monitor/AlarmInputDelay: Determines how long the signal at the Monitor Input
Contact must remain high/low in order to generate an alarm.
(Default = 0.5 Seconds.)
• ResendDelay: Determines how long the AFS-16 will wait to resend an email
message generated by this alarm, when the initial attempt to send notification was
unsuccessful. (Default = 60 Minutes.)
• NotifyUponClear: When this item is enabled, the AFS-16 will send additional
notification when the signal at the Monitor Input contact (Pin 4 on the Control
Module's AUX Connector) returns to the normal (non-alarm) state. (Default = On.)
• EmailMessage: Enables/Disables email notification for this alarm. (Default = On.)
Note:Ifeitherofthe"CopytoAllTriggers"optionsisselected,thenemail
notificationforotheralarmswillbeswitchedOnorOffasindicatedbythis
parameter.
Address1,2,and3: These parameters are used to select which of the three
email addresses defined via the "Email Messages" menu (see Section 5.9.11)
will receive the email alarm notification messages generated by this alarm.
The Address parameters can be used to select one, or any combination of the
addresses defined via the Email Messages menu. (Default = All On.)
Note:IfEmailaddresseshavebeenpreviouslyspecified,thenthetextunder
theparameterswilllistthecurrent,userdefinedemailaddresses.
• Subject: Define the text that will appear in the "Subject" field for email notification
messages generated by this alarm. (Default = "Alarm: Monitor/Alarm Input".)