Chapter 4 Parameters|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11 4-59
When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration
settings. It is valid only when the AC motor drive is running.
When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.
When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).
02.11 Keypad Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read keypad frequency command.
02.12 Communication Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read communication frequency
command.
02.13
The Selections for Saving Keypad or Communication Frequency
Command
Factory Setting: 0
Settings 0 Save Keypad & Communication Frequency
1 Save Keypad Frequency only
2 Save Communication Frequency only
This parameter is used to save keypad or RS-485 frequency command.
02.14 Initial Frequency Selection (for keypad & RS485/USB)
Factory Setting: 0
Settings 0 By Current Freq Command
1 By Zero Freq Command
2 By Frequency Display at Stop
02.15 Initial Frequency Setpoint (for keypad & RS485/USB) Unit: 0.01
Settings 0.00 ~ 600.0Hz Factory Setting: 60.00
These parameters are used to determinate the frequency at stop:
When setting Pr.02.14 to 0: the initial frequency will be current frequency.
When setting Pr.02.14 to 1: the initial frequency will be 0.
When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.