Chapter 4 Parameters|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11 4-27
Parameter Explanation Settings
Factory
Setting
Customer
0: No function
1: AC drive operational
2: Master frequency attained
11.00
Multi-function
Output Terminal
MO2/RA2
3: Zero speed
0
4: Over torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
11.01
Multi-function
Output Terminal
MO3/RA3
7: Operation mode indication
0
8: Fault indication
9: Desired frequency 1 attained
10: Terminal count value attained
11.02
Multi-function
Output Terminal
MO4/RA4
11: Preliminary count value attained
0
12: Over Voltage Stall supervision
13: Over Current Stall supervision
14: Heat sink overheat warning
11.03
Multi-function
Output Terminal
MO5/RA5
15: Over Voltage supervision
0
16: PID supervision
17: Forward command
18: Reverse command
11.04
Multi-function
Output Terminal
MO6/RA6
19: Zero speed output signal
0
20: Warning(FbE,Cexx, AoL2, AUE, SAvE)
21: Brake control (Desired frequency
attained)
0
22: Drive ready
11.05
Multi-function
Output Terminal
MO7/RA7
23: Desired frequency 2 attained
0: No function 0
1: Multi-Step speed command 1
11.06
Multi-function Input
Terminal (MI7)
2: Multi-Step speed command 2
3: Multi-Step speed command 3 0 11.07 Multi-function Input
Terminal (MI8)
4: Multi-Step speed command 4