Chapter 4 Parameters|
4-44 Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
01.05 01.03 01.01
01.06
01.04
01.02
01.00
01.07
01.08
V
/f Curve
Voltage
Frequency
Output Frequency
Lower Limit
Output Frequency
Upper Limit
The limit of
Output
Frequency
Mid-point
Freq.
Maximum
Output
Frequency
Maximum
Output
Voltage
Mid-point
Voltage
Minimum
Output
Voltage
Minimum
Output
Freq.
Maximum Voltage
Frequency
(Base Frequency)
01.08
Output Frequency Lower Limit
Unit: 0.1
Settings 0.0 to 100.0% Factory Setting: 0.0
The Upper/Lower Limits are to prevent operation errors and machine damage.
If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the
Output Frequency will be limited to 50Hz.
If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01.05) is
set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01.07).
The Output Frequency Lower Limit value = (Pr.01.00 * Pr.01.08) /100.
01.09 Acceleration Time 1 (Taccel 1) Unit: 0.1/0.01
01.10 Deceleration Time 1 (Tdecel 1) Unit: 0.1/0.01
01.11 Acceleration Time 2 (Taccel 2) Unit: 0.1/0.01
01.12 Deceleration Time 2 (Tdecel 2) Unit: 0.1/0.01
Settings 0.1 to 600.0 sec / 0.01 to 600.0 sec Factory Setting: 10.0
Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals MI3~
MI12 to 7 (set Pr.04.05~Pr.04.08 to 7 or Pr.11.06~Pr.11.11 to 7).
01.19 Accel/Decel Time Unit
Factory Setting: 0
Settings 0 Unit: 0.1 sec
1 Unit: 0.01 sec