Honeywell UMC800 Network Card User Manual


 
Specifications
I/O Module Configuration
Release F UMC800 Controller Installation and User Guide 95
4/01
Component Parameter Description
Inputs per Module
6 (ID 3) or 16 (ID B) dry
contact
Logic Inputs
(Module ID 3 and B)
Switching Voltage
5 Vdc
Switching Current
5 mA
Digital Outputs
AC Outputs
(Module ID 8)
DC Outputs
(Module ID 7)
Outputs per Module
6 6 (current sinking)
Operating Voltage
15 Vac to 240 Vac 10.2 Vdc to 26.4 Vdc
Output Type
SSR (Triac) NPN open collector
Peak Voltage
264 Vac 40 Vdc
AC Frequency
47 Hz to 63 Hz N/A
ON Voltage Drop
<1.5 Vac (>0.1A)
<3.0 Vac (<0.1A)
1.5 Vdc maximum
Maximum Load
Current
0.5 A per point or
2 outputs at 2.0 A and
4 outputs at 0.5 A
0.3 A per point
Maximum Leakage
Current
4 mA (240 Vac, 60 Hz)
1.2 mA (100 Vac, 60 Hz)
0.9 mA (100 Vac, 50 Hz)
0.1 mA @ 40 Vdc
Maximum Inrush
Current
10 A for 10 ms 1 A for 10 ms
Minimum Load
10 mA 0.5 mA
Base Power required *
20 mA / ON pt. 250 mA
maximum
100 mA maximum
5 V
OFF to ON Response
1 ms 1 ms
ON to OFF response
1 ms +1/2 cycle 1 ms
Fuses
5 x 20mm
1 per output, 1.5 A slow blow 1 per output
1 A fast blow