Honeywell UMC800 Network Card User Manual


 
UMC800 Overview
Feature Summary
4 UMC800 Controller Installation and User Guide Release F
4/01
through the Configuration port allows remote access to the controller via the Control Builder and User
Utility programs. This will enable trouble shooting, configuration changes and firmware upgrade.
The optional communications board adds two bi-directional, multi-drop RS 485 serial communication
interfaces to the controller CPU module. The COMM A port uses Modbus RTU protocol and is a
master/slave link allowing up to 31 controllers to be connected to a single host computer. The computer
initiates all communication. COMM B port allows the controller to operate as a master device to up to 16
slave Modbus compatible devices. Data transferred through this port is integrated into the users control
strategy through read and write function blocks. Applications might include writing controller data (set
points, process variables, etc.) to a strip chart recorder to produce a hard copy of process performance, or to
read data from other controllers.
Feature Summary
Up to 16 control loops, including:
Proportional Integral Derivative (PID),
ON/OFF,
Three Position Step Control (TPSC), and
Carbon Potential.
Auto-tuning for each control loop
Up to 64 Universal Analog Inputs
Up to 16 Analog Outputs
Up to 96 Digital Inputs/Outputs
Up to 50 Recipes with up to 50 variables each
Up to 4 Setpoint Programmers, 3500 total segments
Setpoint Profile and Recipe storage, up to 70 programs
Setpoint Scheduler, 10 stored schedules
Function Block Graphic Configuration with up to 250 blocks
Large assortment of algorithms for combination of analog and logic functions
Extensive Alarm and Event monitoring
Operator interface with a selection of graphic displays
Carbon Potential, Dewpoint and Relative Humidity Control
Optional 3-1/2 floppy disk drive for data archiving, setpoint program and recipe storage
Universal Power (100 to 240 Vac or Vdc) or 24 VA RH)
UL, CE, and CSA approved, Y2K compliant C/DC (optional)
Industrial Operating Range (0 °C to 55 °C, 10 % to 90 %
UL, CE, and CSA Approved, Y2K compliant