Powerware SOLA 4000 Network Card User Manual


 
SOLA 4000 - Technical Data
JUE 401269
106
IG. 2.1 - Rectifier Data
2 Rectifier Data
Technical Data / Rectifier Data
Type SOLA 4000
10 15 20 30 40 60 80 100 120
Input voltage
Tolerance
with reduced output (DC) voltage
refer to system data
refer to system data
-20 %
Input frequency
Tolerance
refer to system data
± 10 %
Rated input power with charged battery
- [kVA]
10,8 16 21,3 32 42,7 64,1 84,8 106 127,4
Rated input current with charged battery
(380 V) [A]
16,4 24,6 32,7 49,2 65 97,5 128,5 160,7 193
Maximum input power
- [kVA]
13,5 20 26,9 39,8 53,5 80 105 132 158
Maximum input current, input voltage = 380 V
- [A]
20,5 30,8 40,8 61,2 81,5 122 160,5 201 241
Input power factor
( nom. load, input voltage = 380V)
~ 0,83 lag.
Output control characteristics I/U characteristic, boost charge possible
Rated output voltage
- Lead-Acid batteries
- Ni-Cd batteries
432 V/DC
436 V/DC (depending on number of cells)
Soft start ~ 10 sec.
Floating voltage regulation with load between 0
and 100%
1 %
Output voltage ripple with battery disconnected
RMS 1 %
Max. batt. recharging current with nom. load
- [A]
5 7,5 10 15 20 30 40 50 60
Battery charging current limitation
Complies with battery manufacturer's recommendations,
standard setting approximately 10% of rated battery capacity