Powerware SOLA 4000 Network Card User Manual


 
JUE 401267
80
SOLA 4000 - Operating Panel
LOAD PERCENTAGE
The actual load is indicated by LEDs as a percentage of the nomi-
nal load.
All LEDs off => Actual load = 0 - 10%
Green LED 20% cont. illumin. => Actual load = 10 - 30%
Green LED 40% cont. illumin. => Actual load = 30 - 50%
Green LED 60% cont. illumin. => Actual load = 50 - 70%
Green LED 80% cont. illumin. => Actual load = 70 - 90%
Green LED 100% cont. illumin. => Actual load = 90 - 100%
Red LED 125% cont. illumin. => Actual load = 100 - 125%
- The UPS is in an overload condition.
- The buzzer is beeping continually and cannot be muted.
LED 29
COMMON ALARM
Red LED continually illuminated and BUZZER beeping fast =
any of the following conditions:
- Inverter Failure
- Battery Switch Open
- Low Battery
- Rectifier Failure
- Paralleling Fault
- Inverter not synchronised (with the bypass supply or internal
oscillator)
- Retransfer blocked
- Overtemperature
- Battery Test Failed
- Inverter not Feeding and bypass off (not active for hot-
standby)
- Bypass system not available (but bypass of this unit is avail-
able when more than one bypass is installed)
• Yellow LED continually illuminated and BUZZER beeping
slowly = any of the following conditions:
- Mains Failure (rectifier)
- Mains Failure (bypass)
- Battery Discharging
- Bypass not available
- Overload
- Load on Bypass (SSB closed)
- Inverter not synchronised (with the bypass supply )
- Auxiliary Alarm
Otherwise the LED is off
LED 30
BOOST CHARGE
Green LED on = Boost charge active
Otherwise LED is off.
2 LED Indication