Powerware SOLA 4000 Network Card User Manual


 
SOLA 4000 - Installation and Initial Start-Up
JUE 401265
22
Version 1 SOLA 4000 with Common Input for
Rectifier and Bypass
Input Cables / Fuses
Type
SOLA
4000
Input
cables
[mm²]
Input
fuses
[A]
earth
cable
[mm²]
10 4x10 25 16
15 4x10 35 16
20 4x16 50 16
30 4x25 63 25
40 4x35 100 25
60 4x35 125 25
80 4x70 160 50
100 4x70 200 50
120 4x120 250 70
TAB.1.2.1 UPS input cables
and fuses, version 1
Output / Battery Cables and Max. Cur-
rent Ratings for Battery Overcurr. pro-
tection
Type
SOLA
4000
Battery
cables
[mm²]
Output cables
[mm²]
Max. inv. input
current
(Vdc=320V)
10 2x16 4x10 25
15 2x16 4x10 40
20 2x25 4x16 50
30 2x25 4x35 75
40 2x35 4x25 100
60 2x50 4x35 150
80 2x70 4x50 200
100 2x95 4x70 250
120 2x120 4 x120 300
TAB.1.2.2 UPS output cables and fuses, version 1
1 Installation